51. Synchronous impedance method of finding voltage regulation of an alternator is called pessimistic method because?
- It gives regulation value higher than its actual found by direct loading
- armature reaction is wholly magnetising
- it is simplest to perform and compute
- it gives regulation value lower than its actual found by direct loading
52. An alternator is supplying a load of 300 kW at a power factor of 0.6 lagging. If the power factor is raised to unity, how many more kW can alternator supply?
- 300 kW
- 100 kW
- 150 kW
- 200 kW
53. The per phase D.C. armature resistance of an alternator is 0.5 Ω. The effective A.C. armature resistance would be about?
- 0.25 ohm
- 0.5 ohm
- 1 ohm
- 0.75 ohm
54. Two alternators A and B are sharing the inductive load equally. What will happen when the excitation of A is increased?
- Current delivered by A will increase and of B will decrease
- Current of A will decrease and of B will increase
- Both will continue to share the load equally
- None of the above
55. Zero power factor method for an alternator is generally used to determine
- efficiency of alternator
- synchronous impedance of alternator
- voltage regulation of alternator
- All of the above
56. For cooling of large size generators hydrogen is used because
- it offers reduced fire risk
- it is light in weight
- it is of high thermal conductivity
- All the above
57. A salient pole synchronous generator connected to an infinite bus power will deliver maximum power at a power angle of
- δ = 0°
- δ = 90°
- δ = 30°
- δ = 45°
58. The angle between induced emf and terminal voltage on no-load for a single phase alternator is
- 180°
- 90°
- 0°
- 270°
59. The field winding of an alternator requires
- DC supply
- AC supply
- Pulsating DC
- Any of the above
60. Voltage regulation of an alternator may be negative where
- the load power factor is lagging
- the load power factor is leading
- it is loaded beyond its full load capacity
- the machine is run at very low loads