Circuit Breakers MCQs

41. A three-phase, 33 kV oil circuit breaker is rated for 1200 A, 2000 MVA, 3s. The symmetrical breaking current is

  1. 1200 A
  2. 3600 A
  3. 35 kA
  4. 104.8 kA

Answer
Answer. c

42. In a circuit breaker, the time duration from the instant of the fault of the extinction of arc is known as

  1. Total clearing time
  2. Operation time
  3. Protection time
  4. Recovery time

Answer
Answer. a

43. In an indoor substation for 220 kV, the circuit breakers will be of the type

  1. Oil
  2. Air break
  3. SF6
  4. Vaccum

Answer
Answer. c

44. Resistance switching is normally employed in

  1. All breakers
  2. Bulk oil breakers
  3. Minimum oil breakers
  4. Air blast breakers

Answer
Answer. d

45. Which is the preferred type of C.B. to be installed in the EHV system?

  1. Vacuum C.B.
  2. Air blast C.B.
  3. Bulk oil C.B.
  4. None of these

Answer
Answer. b

46. Circuit breaker is used for which of the following

  1. Voltage control
  2. Power control
  3. Frequency control
  4. Over control protection

Answer
Answer. d

47. Which one of the following is not a routine test of a circuit breaker?

  1. Short circuit test
  2. Dielectric test
  3. Thermal test
  4. DC resistance voltage drop test

Answer
Answer. a

48. The most suitable circuit breaker for interrupting short line fault without resistance switching is

  1. Minimum oil circuit breaker
  2. SF6 circuit breaker
  3. Bulk oil circuit breaker
  4. Air blast circuit breaker

Answer
Answer. b

49. The restriking voltage in circuit breaker is measured in

  1. RMS value
  2. Peak value
  3. Instantaneous value
  4. Average value

Answer
Answer. c

50. The Air Blast circuit breakers for 400 kV system are designed to operate

  1. 0.1 s
  2. 0.5 s
  3. 50 ms
  4. 100 μs

Answer
Answer. c